Owner`s manual

THE CALDERA
Page 42
ALLOWABLE TERMINATION LOCATIONS
Canadian Installations
1
US Installations
2
____________________________________________________________________________________________________
A= Clearance above grade, veranda *min. 12”(30 mm) *min. 12”(30 mm)
porch, deck or balcony
____________________________________________________________________________________________________
B= Clearance to window or door *min. 12”(30 mm) *min. 12”(30 mm)
that may be opened
_______________________________________________________________________________________________
C= Clearance to permanently closed *min. 12”(30 mm) *min. 12”(30 mm)
window
____________________________________________________________________________________________________
D= Vertical clearance to ventilated *min. 20-1/2” (521 mm) *min. 20-1/2” (521 mm)
soffit located above the terminal within from center of termination from center of termination
a horizontal distance of 2’ (61 cm) from
the centerline of the terminal
____________________________________________________________________________
E= Clearance to unventilated soffit *min. 20-1/2” (521 mm) *min. 20-1/2” (521 mm)
from center of termination from center of termination
_________________________________________________________________________________________________
F=Clearance to outside corner *min. 10”(250 cm) *min. 10” (250 cm)
from center of termination from center of termination
____________________________________________________________________________________________________
G=Clearance to inside corner *min. 12-1/2" (318 mm) *min. 12-1/2" (318 mm)
from center of termination from center of termination
____________________________________________________________________________________________________
H= Clearance to each side of centerline 3’ (91cm) within a height 15’ (4.5m) *
extended above meter/regulator assembly above the meter/regulator assembly
____________________________________________________________________________________________________
I= Clearance to service regulator vent outlet 3’ (91cm) *
____________________________________________________________________________________________________
J= Clearance to no mechanical air supply inlet 12” (30cm) 9” (23cm)
to building or the combustion air inlet to any
other appliance
____________________________________________________________________________________________________
K= Clearance to a mechanical air supply inlet 6’ (1.83 m) 3’ (91 cm) above if within 10’ (3 m)
horizontally
____________________________________________________________________________________________________
L= Clearance above paved sidewalk or paved 7’ (2.13 m)† *
driveway located on public property
____________________________________________________________________________________________________
M = Clearance under veranda, porch, deck or 12” (30 cm)‡ *
balcony
____________________________________________________________________________________________________
1
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and
serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:
a) A minimum clearance value determined by testing in accordance with section 2.23.7, or ;
b) A reference to the following footnote: “Clearance in accordance with local installation codes and the requirements of the gas
supplier”
Figure 19