re covery process is supervised at all limes by a
competent person;
recovery equipment and cylinders conform to the appropriate
standards.
•
Pump down refrigerant system, if possible.
• lf
a
vacuum is not
possible, make
a
manifold
so
that
refrigerant
can
be removed
from various parts of the system.
• Make sure that cylinder is situated on the scales before
recovery takes place.
•
Start the recovery machine and operate in accordance with
manufacturer's instructions.
•
Do
not
overfill
cylinders.
(No more
than
80
%
volume
liquid
charge).
•
Do
not
exceed the
maximum
working pressure of
the
cylinder,
even
temporarily
•
When the cylinders have been filled correctly and the
process completed, make sure
that
the
cylinders
and
the
equipment
are removed
from
sile
promptly
and all
isolation valves on the equipment are closed
off.
•
Recovered refrigerant shall not be charged into another
refrigeration system un- less it has been cleaned and
checked.