ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED
ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
CONNECTION TO POWER MAINS
The ventilator is rated for connection to single-phase AC 1~100-230 V 50/60 Hz power mains.
Connect the ventilator to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed
wiring system.
The power cable is connected to the upper terminal block.
LN
L
N
Jumpers for set-up of
the Ventilation mode.
1~100-230 V 50/60 Hz
Ventilation mode setting
Air direction in the Ventilation mode is determined by position of the jumper on the control board.
The circuit board of the controller is located inside the ventilation unit.
Air supply Air exhaust