Tus neeg siv phau ntawv
Table Of Contents
- Safety requirements
- Purpose
- Delivery set
- Designation key
- Technical data
- Design and functioning
- Mounting and set-up
- Connection to power mains
- Technical maintenance
- Troubleshooting
- Storage and transportation regulations
- Manufacturer’s warranty
- Certificate of acceptance
- Seller information
- Installation certificate
- Warranty card
www.blaubergventilatoren.de
KOMFORT Roto EC S6(E)K 200
6
598
373
791
866
140 112
49
67
355
283
125 284
78
159
348
Parameter KOMFORT Roto EC S6K 200 KOMFORT Roto EC S6EK 200
Unit voltage [V/50 (60) Hz] 1~ 230
Maximum unit power (without a heater) [W] 118
Maximum heater power [W] - 700
Maximum unit power [W] 118 818
Maximum unit current (without a heater) [A] 1,0
Maximum heater current [A] - 3
Maximum unit current [A] 1 4
Maximum air flow [m
3
/h] 270
RPM [min
-1
] 1800
Sound pressure level at 3 m distance [dBA] 28
Transported air temperature [°C] -25...+40
Casing material painted steel
Insulation 20 mm mineral wool
Filter
extract G4
supply
G4, F7
Connected air ducts diameter [mm] 125
Weight [kg] 47 48
Heat recovery efficiency [%] 75...92
Heat exchanger type rotary
Heat exchanger material Aluminium
SEC class A
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum
(20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic
components. Never use the unit for dehumidification, for example, of new buildings.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.