KOMFORT Roto EC S6(E)K 200
13
EXTERNAL WIRING DIAGRAM
XS11 X1
1
C
2
NC
3 4
N
5
L
Grey
Black
Yellow/green
Blue
Brown
KH1*
TS1
1 2 1 2
HL
PE
GNDGND 0-10V A B +24V+24V
12
PK1 *
12 1212 12
Boost* CO2* P1* SM1* SM2*
12
CCU*
12 12
**U
**U
LN
N
NC C PE
L
C
NO NO NO
C C C
A B
0-10V +24V +24V
NO GND GND
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Power supply
230 V, 50 Hz
Brown
Yellow
Green
White
Electric shock hazard!
Designation Name Contact type Cable type Note
SM1* Supply air damper actuator NO
2 x 0.75 mm
2
3A, 30DC/~250 AC
SM2 * Extract air damper actuator NO 3A, 30DC/~250 AC
PK1* Contact from fire alarm panel NC Remove the jumper
CCU* CCU control NO 3A, 30DC/~250 AC
P1* External control panel 4 x 0.25 mm
2
Boost* On/Off contacts of the Boost mode NO 2 x 0.75 mm
2
CO2* Outdoor CO
2
sensor 3 x 0.25 mm
2
KH1* Kitchen hood 5 x 0.75 mm
2
*Is not included in the delivery set.
*The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers.
Output parameters: terminals 12-17 - 3 A, 30VDC / ~ 250VAC (“dry contact”).
The maximum cable length from external devices to the terminal block should not exceed 100 meters. The recommended cable cross-section is shown in the table.