Tus neeg siv phau ntawv
Table Of Contents
TECHNICAL DATA
UNIT OVERALL DIMENSIONS mm
A1
A2
A
B
B3
B4
B1
B2
Ø D
Model A A1 A2 B B1 B2 B3 B4 D
BL02 CFH 1500-R/L
BL02 CFH 2500-R/L
1060 838 350 1880 789 600
325 425
18BL03 CFH 3500-R/L 1390 1003 400 2200 890 700
357 439
BL07 CFH 5000-R/L
BL07 CFH 6000-R/L
1520 1218 500 2500 1430 1000
479 690
The full technical data list is stated in the supplied technical data sheet.
The unit is designed for indoor or sheltered use. The installation conditions must prevent ingress of atmospheric precipitations and direct
solar radiation at the ambient temperatures from -35 °C up to +50 °C. Outdoor unsheltered mounting is allowed provided an extra cover
and weather hoods are installed on the air ducts (not included in the delivery set).
The frost protection for the water drainage and connected pipelines must be provided during sub-zero ambient temperatures (if the unit
is equipped with an air cooler). The heat medium temperature in the water heat exchangers (if available) must be sufficient to prevent
their freezing. Hazardous parts access and water ingress protection rating:
• IP54 for the unit motors
• IP42 for the assembled unit connected to the air ducts without extra cover or weather hoods
• IP44 for the assembled unit with connected air ducts, extra cover and weather hoods (specially ordered accessories)
• IP00 for the unit not connected to the air ducts
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
www.blaubergventilatoren.de
BlauAir CFH
5