User manual

OEM Device Configuration Guide
revision 3 — 51
10.2. Device Configuration
For a complete list of configuration options, refer to the Lantronix reference manual. At this point, the
Lantronix box should be ready to act as a gateway between a LAN and a serial device. It is also necessary to
wire and configure each individual device.
For wiring between the hardware and the Lantronix box, a straight through RS-232 cable is used. Also, a 25-
pin/9-pin adapter may be required for certain hardware. The Lantronix box is equipped with a 25 pin male
connector.
Note: Be sure to match the baud rate setting with the baud rate for which the hardware is configured.
1. A start character of 0 should be used, with an end character of 0x0014.
2. For Pyrotronics, an additional RS-232/RS-485 adapter is needed.
3. SDI Automation must be enabled on this panel. This is done via the RAM IV software in RADAUX1 >
SDI Automation > Enable SDI Automation = Yes. When using a D9133 with this device, the D9133
should be connected to the host with a null modem cable.
Device access parity stop
bits
byte
size
flow
control
baud rate
AES IntelliNet (Radionics
6500 output mode)
1
remote odd 2 7 CTS/RTS 1200
Apollo panel remote none 1 8 none 9600/4800/2400/1200
Detection Systems DS7400Xi remote none 1 8 CTS/RTS 2400/9600
Digitize System 3505/3500/
3000
remote none 1 8 none 1200
Notifier panel remote even 1 7 none 2400
Osborne-Hoffman OH-2000 remote none 1 8 CTS/RTS 9600
Pyrotronics
2
remote even 1 7 none 115200/57600/38400/
19200/9600/4800/
2400/1200
Radionics D6600/D6500 remote none 1 8 CTS/RTS 38400/19200/9600/
4800/2400/1200
Radionics D7412/D9412
3
remote none 1 8 none 9600
Zenitel AlphaCom remote even 1 7 none 9600
Visonic remote none 1 8 CTS/RTS 9600