User manual

Intrusion Detection
20 —
revision 3
Wiring
Connect the PC9133TTL-E to the Radionics D9412/D7412 as follows:
Connect the PC9133TTL-E (RJ-45 connector) to the network.
Set Up a Temporary IP Address
Before using the network interface module, you must assign a unique IP address to it. In order to do this,
locate the MAC address on the label.
1. Verify that there is at least one entry in the ARP table. To do so, at the command prompt, type
arp -g
If there are no entries other than the local machine, ping another machine (which must be a host
other than the machine on which you are working) on the network to build the ARP table.
2. Use the ARP command to configure the IP address. Type
arp -s [IP Address] [Ethernet/Hardware Address]
where the IP address is a numerical address and the Ethernet/Hardware Address is the MAC address
found on the label attached to the PC9133TTL-E.
3. Verify that the address was added to the table by typing
arp -g
The ARP command is used only to temporarily associate the IP address with the MAC address. To
permanently assign the IP address, telnet to the device and set it in the server configuration.
Assign the IP Address
1. At the command prompt, telnet to port 1. Type
telnet [IP Address] 1
This first attempt at telnetting will fail.
2. Telnet to port 9999. Type
telnet [IP Address] 9999
This second attempt at telnetting will be successful.
3. Press <Enter> to go into setup mode.
4. Select 0 for Server Configuration.
a. Configure the IP address of the PC9133TTL-E. This is the same IP address used for the Radionics
Intrusion Panel in System Administration
b. If a gateway IP address is needed, select Y and enter the information. This is only needed when
using a WAN. In a LAN, the gateway is not necessary and only needs to be changed if the gateway
IP of the PC is different than that of the PC9133TTL-E host.
PC9133TTL-E connection Panel connection
SDI PWR POWER + (Terminal 32)
SDI A DATA A (Terminal 31)
SDI B DATA B (Terminal 30)
SDI COM COMMON (Terminal 29)