Addressable expansion modules (D8125)
• provide point identification for initiating devices.
• supervise wiring to devices to ensure circuit integrity.
• are used to expand the control/communicator beyond its standard number of on-board initiating zones
or points.
The D8125 module should be connected to the Zonex ports and powered by the control/communicator.
The Octo-relay module (D8129) provides eight programmable Form-C relays. This module is also
connected to the Zonex ports and powered by the control/communicator.
The Command Center is a keypad with an alphanumeric display, capable of distinct fire and burglary tones.
It should be connected to the data bus and powered by the control/communicator.
Note: The Radionics D7412G and D9412G require firmware version 6.20.
3.2.1 Configure the Radionics D7412G/D9412G
Configuration of the D7412/D9412 must be done through the software provided by the manufacturer. A
D9133DC serial interface module is required (with the address set to 88). This device can be connected to
the host computer via a NULL modem cable. For more information on RAM IV, refer to the Radionics RAM
IV manual. Currently, RAM IV is used for:
• Initial setup of the system (zones, areas, users, schedules, authority levels, functions, command centers,
etc.)
• Adding/deleting/modifying users (also can be done through keypad commands on the panel)
• Changing zone properties, schedules, etc.
The panel needs to be configured for SDI Automation. This is also done via the RAM IV software. Under
RADAUX1 > SDI Automation, Enable SDI Automation needs to be set to yes.
Important: Do not install the RAM IV software on the same computer as the Detection
Systems Configuration software! Doing so will cause damage to your computer.
3.2.2 Serial Interface Module D9133
Communication between B.A.S.I.S. and the D9412/D7412 requires the D9133 (serial interface module).
This device can be connected to the host computer via a NULL modem cable. Set the address to 80 (the four
address jumpers need to be off).
3.2.3 Network Interface Module PC9133TTL-E
The PC9133TTL-E is used for a network connection to the Radionics panel in place of the D9133 and
Lantronix box. Set the address to 80 for SDI automation (no jumpers installed). The address configuration is
read only at power-up, so if a change is made, cycle power to the device.