A DB-25 or DB-9 cable may be used. Connect the pins as follows:
1.3.2 Programming the Fire Panel
The fire panel must be programmed in order to recognize downstream devices such as intelligent/
addressable detectors and modules, Panel Circuits, and Notification Appliance Circuits (NACs). Use the
keypad connected to the panel for programming. For more information, refer to the Notifier documentation.
1. To begin programming, press [ENTER.].
2. Press [1] to enter the programming menu. At this point, if the panel starts beeping, you may silence it by
pressing the [ACKNOWLEDGE SCROLL DISPLAY] button.
3. You will then be prompted for a password. Enter 00000.
4. Press [1] to enter the Basic Program menu.
5. Press [1] to start Auto-programming. This option identifies all addressable devices connected to the
panel. You will be prompted to accept or remove the device from memory as they are found by the
panel.
6. After this process is complete, a summary of programmed devices will be displayed. Press [Enter] to
continue. If any alarms are generated, you may silence them again. Configuration of the panel is
complete.
TB14 DB-25 pin DB-9 pin
TX 3 (Receive) 2
RX 2 (Transmit) 3
REF 7 (Ground) 5