Specifications

C•CURE apC/L Technical Manual
Testing the apC/L Installation
7-2
Testing Readers
This section describes the test procedures for magnetic stripe and Wiegand
readers. You can bench test readers by not connecting them to the apC/L.
When you complete the test, reset the address switch to its original setting.
To test a reader for normal operation:
1. Set the reader address switch to 9.
2. Power up the reader. (Use 12V DC from the apC/L or a regulated power
supply.)
For standard RM-2 readers, the LEDs on the reader indicate whether the test
procedure is successful. The next 17 steps describe each LED response. If
your reader does not have a keypad, perform only Steps 17 and 18.
3. Press the 1 key. The red LED lights up.
4. Press the 1 key again. The red LED flashes slowly.
5. Press the 1 key again. The red LED flashes rapidly.
6. Press the 1 key again. The red LED goes out.
7. Press the 2 key. The amber LED lights up.
8. Press the 2 key again. The amber LED flashes slowly.
9. Press the 2 key again. The amber LED flashes rapidly.
10. Press the 2 key again. The amber LED goes out.
11. Press the 3 key. The green LED lights up.
12. Press the 3 key again. The green LED flashes slowly.
13. Press the 3 key again. The green LED flashes rapidly.
14. Press the 3 key again. The green LED goes out.