Specifications
C•CURE apC/L Technical Manual
Setting Up the apC/L Panel
6-7
SW3:8 Unit Low-Address or Unit Hi-Address. When switch 8 is set OFF
(Default), the unit switch (SW1) addresses the apC/L as units 1 through 16.
When switch 8 is ON, the unit switch (SW1) addresses the apC/L as units 17
through 32.
Setting apC/L Jumpers
The apC/L uses several jumpers. Some of these control communications
features of the apC/L and they must be properly set for the apC/L to function.
Most of the jumpers are two-post and are either open or closed. Some jumpers
have three posts for an A or B setting. You can close section A or B of a three-
post jumper, by installing a jumper housing between the center post and the A
or B post.
See Figure 6.1 for the location of the jumpers on the apC/L and Table 6.3 for
the settings of the apC/L jumpers and their function.
Table 6.2 Baud Rate Settings
Baud Rate SW3:5 SW3:6 SW3:7
1200 ON OFF OFF
2400 OFF ON OFF
4800 ON ON OFF
19,200 OFF OFF ON
2400 x.25 ON OFF ON
4800 x.25 OFF ON ON
9600 x.25 ON ON ON
9600 OFF OFF OFF
apcl.bk Page 7 Monday, May 15, 2000 3:21 PM