Specifications
C•CURE apC/L Technical Manual
Wiring Inputs to the RM
4-19
These wires may be no longer than 25 feet for mullion and 500 feet
for Wiegand readers. Do not run these lines near high voltage lines or
motorized equipment (such as elevators or compressors).
4. Connect the data wires to the pins on the personality module as
follows:
Connect the apC/L +TXD/+RXD data wire to pin 2 of P1
Connect the apC/L -TXD/-RXD data wire to pin 3 of P1
Do not connect the drain wire at the RM or MRM
5. Connect the power wires to the pins on the personality module as
follows. See Appendix B for information about calculating maximum
wire lengths.
Connect the +12V power line to pin 1 of P1
Connect the ground wire to pin 4 of P1
6. If the door monitor input is not used, place a 1K ohm resistor across
the unused contacts. To use the door monitor input, connect the door
monitor wires to the pins on the personality module as shown in
Figure 4.9.
For an RM:
Connect one lead to pin 4 of P5
Connect the other lead to pin 5 of P5
For an MRM:
Connect one lead to pin 8 of P5
Connect the other lead to pin 9 of P5
7. If the exit push-button input is not used, place a 1K ohm resistor
across the unused contacts. To use the door monitor input, connect the
exit push-button wires to the pins on the personality module as shown
in Figure 4.9.
Note Reader data lines and power lines must be separate pairs. Tie the
drain wire for the data pair to the earth ground at the apC/L end
only.