Specifications
C•CURE apC/L Technical Manual
Wiring Card Readers
4-18
Figure 4.9 Request to Exit and Door Contact Wiring
2. If ARMs are used, pull the positive and negative terminal wires. Each
should be a shielded twisted pair Belden #9462 with a maximum
length of 25 ft. (7.6 meters).
3. Wiring standard Sensormatic readers
Remove the reader backplate and feed the wires through the hole in
the backplate.
Wiring Mullion and Non-Sensormatic readers
On the RM: Plug the reader’s sensor wire connector into J3.
On the MRM: Plug the reader’s sensor wire connector into P3.
Twisted pair 18AWG (0.902mm) Belden #8461
or 22AWG (0.357mm) Belden #8442
Max 2000 ft
Note: If the exit button or door contact is not
used, place a 1K ohm resistor across the inputs.
P5
Normally Open (Door contact or Exit)
Contact open =1KΩ =Secure
Contact closed =500Ω =Alarm
Short circuit <400Ω =Trouble
Open circuit >21KΩ =Trouble
Normally Closed (Door contact or Exit)
Contact closed =1KΩ =Secure
Contact open =2KΩ =Alarm
Short circuit <400Ω =Trouble
Open circuit >21KΩ =Trouble
1 2345 67