Specifications
C•CURE apC/L Technical Manual
Wiring Card Readers
4-16
Figure 4.8 ARM-1 Wiring for AC Door Strike
P5 on the RM-4 module
1
2
1
2
1
2
3
ARM-1
P2
P1
(normally open)
or
(normally closed)
Local
ac power
supply
AC
door
strike
MOV (World Products Inc. SNR-D56K2
Twisted, shielded 22 AWG(0.357mm) Belden
#9462, Maximum distance: 25 ft. (7.6 m)
Shield tied to chassis ground point on RM-4
Contacts rated for:
Voltage
Resistive Inductive
125V 0.4A 0.2A
30VDC 2.0A 1.0A
(com)
or equivalent)
apcl.bk Page 16 Monday, May 15, 2000 3:21 PM