Specifications

C•CURE apC/L Technical Manual
Installing the Auxiliary Relay Modules (ARM-1)
4-15
cathode must be on the positive side of the strike. The ARM-1 wiring
for an installation with DC power is shown in Figure 4.7.
Figure 4.7 ARM-1 Wiring for DC Door Strike
If the power supply is AC, install a varistor (World Products, Inc. #SNR-
D56K2 or equivalent) across the door strike to suppress noise. Figure 4.8
shows the ARM-1 wiring for an installation with AC power.
P5 on the RM-4 module
1
2
1
2
1
2
3
ARM-1
P2
P1
(normally open)
or
(normally closed)
Local
power
supply
+
-
DC
door
strike
Motorola or other manufacturer diode
type 1N 4933
Twisted, shielded 22 AWG(.357mm) Belden
#9462, Maximum distance: 25 ft. (7.6 meters)
Shield tied to chassis ground point on RM-4
Contacts rated for:
Voltage
Resistive Inductive
125V 0.4A 0.2A
30VDC 2.0A 1.0A
(com)
+
-
Note The wiring for Relay Outputs is configured the same way as
ARM-1