Installing the Auxiliary Relay Modules (ARM-1)
4-13
To install the ARM-1:
1. The ARM-1 is 1.7” by .75” (4.3 by 1.91 cm) in size. It is mounted
inside the protected area no more than 25 ft. (7.6 m) from the RM.
2. Pull a twisted, shielded pair of 22 AWG (0.357 mm) Belden #9462 in
between each ARM-1 and the reader personality module. The
maximum length for this cable is 25 ft. (7.6 m).
3. Pull a twisted pair of wires between the ARM-1 and the associated
relay controlled device.
4. With the shielded wire, connect pin 1 of P5 on the RM-4 module to
Pin 1 of P2 on the ARM-1. Then connect Pin 2 of P5 on the RM-4
module to pin 2 of P2 on the ARM1.
You can connect a second ARM-1 to the RM-4. P5-1 on the RM-4
module is the common pin for either ARM-1. P5-2 is the output for
the first ARM-1 and P5-3 is the output for the second. (Figure 4.6)
See Figure 4.8 for the layout of connector P5.
n
Wire the ARM-1 to the RM-4 as follows:
ARM #1 - P2-1 to P5-1
P2-2 to P5-2
ARM #2 - P2-1 to P5-1
P2-2 to P5-3