Specifications
C•CURE apC/L Technical Manual
Setting Up a Reader
4-9
Setting Up a Reader
Setting Reader Type for an RM-4 Personality
Module
Set the reader type using DIP switch SW3-1 on the RM-4. If you are
setting up a magstripe reader, set SW3-1 to the Open (Off) position. If you
are connecting a Wiegand or proximity reader, set SW3-1 to Closed (On).
If you are setting up the last reader on a multidrop line, set SW3-5 to On.
Use the information in the following table to set the reader type.
There are 5 other reader configuration switches. Table 4.2 indicates what
each switch controls and how to set them for your site.
Setting the Reader Address for an RM-4 or
Personality Module
The SW1 switch determines the communication address for the readers.
Each reader connected to an apC/L must use either 1 or 2 as its address. If
SW1 is set to 0 or if SW1 is set between two address numbers, the red
LED on the reader flashes rapidly when the reader is turned on. Use a
screwdriver to turn the arrow on the switch to the desired address. The
system reads the address switch setting after several seconds.
Reader
Description
Switch Number Switch Setting
Magnetic Stripe SW3-1 Open (OFF)
Wiegand/Proximity SW3-1 Closed (ON)
Note The RM must be powered off then back on for changes to take
effect.
Note On the RM personality module it is a 16-position rotary switch.
apcl.bk Page 9 Monday, May 15, 2000 3:21 PM