Specifications

C•CURE apC/L Technical Manual
Mounting the apC/L Cabinet
3-4
Connecting the apC/L Input Voltage
The apC/L is shipped with an external transformer. The Class-2 transformer is
connected to the apC/L with the supplied cable assembly. The transformer
will only accept 120 VAC, 60 Hz. The cable assembly consists of two Red and
one Green wire. Connect the Red wires to the transformer connectors marked
(
AC). Connect the green wire to the middle connector marked (GND) then to
P8 on the apC/L which is marked with an ~ for AC and a ground symbol for
the ground connection.
Connecting the Optional Backup Battery
The apC/L has a built-in battery charging circuit. A 4 Amp-hour battery and
cable are supplied with the purchase of the battery back-up option. Connect
the red lead of the cable to the positive (+) side of the battery and the black
lead to the negative (-) side of the battery. Connect the other end of the battery
cable to P9 on the apC/L which is marked positive (+) and negative (-).
CAUTION
The output of the transformer is internally fused. Do
not short the output of the transformer.
The AC input is fused with a 5A, AGC5 fuse; replace it
only with a fuse of the same type and rating. Do not cut
or remove the ground lug from the transformer.
CAUTION
The battery output is fused with a 3A AGC3 fuse. For
continued protection, replace with the same type and
rating fuse.
apcl.bk Page 4 Monday, May 15, 2000 3:21 PM