Specifications
C•CURE apC/L Technical Manual
Equipment Wiring Requirements
2-3
Table 2.2 Equipment Wiring Requirements
* For plenum or underground applications, use Manhattan M63995 for 2 pair only, (host wiring) 150 ohm, 8.8pf/ft
or Belden 89182 for 1 pair (reader wiring) 22AWG, 100 ohm, 12.95pf/ft.
Signal From To Belden
#
Gauge #
Prs
Shielded Max
Length
RS-232 Comm Host apC/L 9855 22 2 Yes 50 ft.
RS-232 Comm (5-
wire)
Host apC/L 8303 22 3 Yes 50 ft.
RS-485 Comm Host apC/L 9842* 24 2 Yes 4000 ft.
Comm apC/L RM-4 9841* 24 1 Yes 4000 ft.
Power apC/L RM-4 8442/8461 22/18 1 No See Appen
B
Control apC/L/
ARM
Strike 8641 18 1 No See Appen
B
Supervised
Input
Input
Module
Contact/
Switch
8442/8461 22/18 1 No 2000 ft.
Request-to-exit RM-4 Switch 8442/8461 22/18 1 No 2000 ft.
Door contact RM-4 Contact 8442/8461 22/18 1 No 25 ft.
Relay RM-4 ARM 9462 22 1 Yes 25 ft.
Reader
Data
RM-4 Wiegand/
Prox Read
Head
9536 22 3 Yes 500 ft.