Specifications

C•CURE apC/L Technical Manual
Configuring OEM Modems
F-9
OEM HyperTerminal Edits for 4-Wire Leased
Lines
From a HyperTerminal Session you will type the following commands:
ATL6 <ENTER> (Lists the S-Registers)
ATS18=0 <ENTER> (Sets the ATS18 Register to 000)
ATS19=0 <ENTER> (Sets the ATS19 Register to 000)
AT&W <ENTER> (Stores the changes you just made to the Registers)
ATL6 <ENTER> (Verify your 18 and 19 Registers are now "000")
Note You must switch the Dip Switch #10 to the UP position in order
for your HyperTerminal session to work properly. Ensure that
after these changes are made that you place Dip Switch #10 back
to the DOWN position. It is normal to not see the commands as
you type them. The only response you will see in your session is
after you press <ENTER> following the list s-register command)
S0 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S13 S18 S19 S24 S25 S30
000 043 013 010 008 004 055 004 006 007 080 037 030 001 020 000 000
S0 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S13 S18 S19 S24 S25 S30
000 043 013 010 008 004 055 004 006 007 080 037 000 000 020 000 000
apcl.bk Page 9 Monday, May 15, 2000 3:21 PM