Specifications
C•CURE apC/L Technical Manual
Testing the apC/L Installation
7-4
20. Press the 7 key to test supervised input number 2. The LED response
indicates the conditions listed in the previous table.
21. Press the 8 key to test the tamper switch. If the tamper switch is
depressed, the red LED is off. When the switch is released, the red LED
lights up.
RM LEDs
Each RM reader has three LEDs: red, green, and amber. The various
conditions indicated by these LEDs are described in Table 7.1.
Table 7.1 Reader LED Indications
Red LED Amber Green Indication
Brief flash Brief flash Brief flash Power up
Off Off Off Online (software flag enabled)
Off On Off Online
On Off Off Offline or reader tamper
Solid for 1 sec. Off Off Access denied
Fast flash for 2
sec.
Off Off Access denied (Software Flag
Enabled)
Off Off On Access granted or door unlocked
(Software Flag Enabled)
Off Off Fast flash Access granted
Off Off Slow flash Door unlocked
Off Slow flash Off Enter second card (escorted access
only)
Off Fast flash Off Enter PIN
Off Fast flash Off Enter floor # (systems configured
for elevator control only)
apcl.bk Page 4 Monday, May 15, 2000 3:21 PM