Keep CAT 5 cable as far away as possible from potential sources of EMI, such as electrical cables, transformers and
light fixtures. Do not tie cables to electrical conduits or lay cables on electrical fixtures.
Always test every installed segment with a cable tester. “Toningalone is not an acceptable test.
Always install jacks so as to prevent dust and other contaminants from settling on the contacts. The contacts of the
jack should face up on the flush mounted plates, or left/right/down on surface mount boxes.
Always leave extra slack on the cables, neatly coiled in the ceiling or nearest concealed location. Leave at least five
feet at the work outlet side and 10 feet at the patch panel side.
Choose either 568A or 568B wiring standard before beginning. Wire all jacks and patch panels for the same wiring
scheme. Do not mix 568A and 568B wiring in the same installation.
Always obey all local and national fire and building codes. Be sure to firestop all cables that penetrate a firewall. Use
plenum rated cable where it is required.