UPS Power Status Alert This alert will be triggered when the UPS power status changes
between on line, on battery, and low battery. This status will only be monitored on the
Applicable UPS(es) you select.
Environment and Power Alert(next section).
Alarm Sensor Alert(next section).
7.2.3 Configuring environment and power alert type
This alert type monitors UPSes, RPCs, power devices, and EMD environmental devices.
Select Environment and Power Alert to activate.
Specify which Sensor Type to alert on (Temperature, Humidity, Power Load and Battery Charge).
Set the levels at which Critical and/or Warning alerts are to be sent. You can also specify High
and/or Low Set Points for sending alerts and the Hysteresis to be applied before resetting off
the alerts.
Note Specify the Set Point values are in Degrees Centigrade for Temperature, Amps (Current)
for Power Load, and % (Percentage) for both Humidity and Battery Charge.