User guide

Introduction and Overview
24 BLACK BOX ® Advanced Console Server
Working inside the BLACK BOX ® Advanced Console Server
Do not attempt to service the BLACK BOX ® Advanced Console Server yourself, except when
following instructions from Black Box Technical Support personnel. In the latter case, first
take the following precautions:
Turn the BLACK BOX ® Advanced Console Server off.
Ground yourself by touching an unpainted metal surface on the back of the equipment
before touching anything inside it.
Ground yourself by touching an unpainted metal surface on the back of the equipment
before touching anything inside it.
Important! Keep your BLACK BOX ® Advanced Console Server away from
heat sources and do not block cooling vents.
Important! The BLACK BOX ® Advanced Console Server product (DC
version) is only intended to be installed in restricted access areas (Dedicated
Equipment Rooms, Equipment Closets or the like) in accordance with Articles
110-18, 110-26 and 110-27 of the National Electrical Code, ANSI/NFPA 701,
1999 Edition.
Use 18 AWG or 0.75 mm2 or above cable to connect the DC configured unit to
the Centralized D.C. Power Systems.
Install the required double-pole, single-throw, DC rated UL Listed circuit
breaker between the power source and the BLACK BOX ® Advanced Console
Server DC version. Minimum Breaker Rating: 2A. Required conductor size: 18
AWG.