Page 21 of 52
• Now light all other gas appliances in the home and run tests 1-3 again.
• Record your results in the check sheet.
• THE PRESSURE AT ALL TIMES MUST BE WITHIN 1MBAR OF THE
DATAPLATE READING
• IF THE TEST FAILED: If it is not possible to maintain the pressure at
the required level, TRANSCO, BORD GAIS or the propane supplier must
be called to adjust the governor to the house before the appliance can
be commissioned further.
• IF THE TEST PASSED: Disconnect the pressure gauge, replace the
pressure test point sealing screw and test the appliance for gas
soundness. Insert the front shelf.
CHECK THE FLUE SYSTEM
• Turn the appliance to the maximum setting. Leave the appliance for 10
minutes and then test that all the products of combustion are entering
the flue by traversing the perimeter of the fireplace opening or canopy
using a smoke generator e.g. smoke matches.
COMPLETE THE COMISSIONING
• The customer should be shown in detail how to operate the appliance
and the installation and user manual given to the customer.
• The customer must also be made aware that the appliance must be
serviced every 12 months and that chimney or flue system should be
checked regularly to ensure the appliance operates at optimum
performance.