Technical data

Page 16 of 44
Fitting the Enclosure
This fire is supplied with an enclosure and integral burner.
IMPORTANT: The appliance is supplied with a fully tested and working gas
burner. There is no need to dismantle the burner. This could result in damage
to the fire which is not covered by the warranty. No connections should be
removed or broken. Removal of any connections will result in the
warranty being invalidated.
The Fire requires 3 connections:
1. GAS SUPPLY.
The fire has an 8mm inlet via an isolation valve. The fire also includes
a pressure test point elbow to test inlet pressure. The gas pipe work
should be routed into the enclosure via the available access holes. If
the gas pipe work is over 1.5mtrs in length it is recommended that the
pipe work is increased in diameter from this point to 15mm and
possibly 22mm depending on the length to the meter. This will ensure
a stable gas supply.
2. HARD WIRE REMOTE.
The hard wire remote has a switch connected. This cable should be
routed from the appliance to a position which is suitable for the user.
If it is required to remove the switch plate in order to install into the
wall great care must be taken when removing the switch. The switch
has a “top” marked on it. The cables must be fitted back in the same
sequence otherwise remote damage will occur.
3. MAINS VOLTAGE
This is via a black cable. This must be fitted to a 3A 240V fused spur
supply which is within access of the user should the fuse need
changing. This is the power source for the remote control system.
Great care must be taken when handling the burner and hard wire system.
If using with the optional Gather, dry fit the gather to the enclosure taking note
of where the gather and enclosure overlap. In some installations it may be
possible to insert the gather into the opening and lift up to allow space to slide
the enclosure in. This reduces the need for a very large builders opening.