Technical data

Page 33 of 56
Quick Reference Fault Diagnosis
Symptom Check List Tick
The system “beeps”
all the time.
There is a fault diagnosis system built into the battery remote.
The remote gives out a sequence of “beeps”. This is a code which
indicates a fault. See page 38 for details.
Check spark lead is connected properly.
Appliance clicks but
no spark or weak
spark.
Check spark electrode is in the correct area and the gap correctly
distanced to the pilot.
Check for a good spark. Check the spark is in the right area.
Check that the ventilation is not too strong and drawing the gas
away from the pilot.
Appliance sparks
but does not light
pilot.
Check that there is gas at the input and at the pilot.
Check that remote valve is operating correctly.
Check isolation tap/shut off is open.
If there is no gas.
Check for blockages in the gas pipes.
Check for a good spark.
Check the spark is in the right area.
Check that the ventilation is not too strong and drawing the gas
away from the pilot.
If there is gas but
pilot does not light
Check the pilot gas slot is clear.
Check the pilot flame is heating the thermocouple.
Check the thermocouple nut is properly tightened into the valve.
Check that the pilot lights early on ignition clicks.
Pilot lights but does
not light main
burner
Check ventilation is not too strong and drawing the pilot flame
away from the thermocouple.
When using LPG Bottles ensure bottle is not empty. To run this
appliance on bottles a minimum of 2 x 47KG bottles with a
changeover valve is required. The bottles must have a suitable
regulator.
Check thermocouple nut is properly secured to the valve.
Check ventilation is not too strong and the flame is not blowing
off the thermocouple.
Burner lights but
turns off after a few
minutes
Check gas pressure is correct and maintained at constant level –
especially with other appliances in the home working.