Specifications

4
PRODUCT APPLICATION
CONSTRUCTION
The water purifier is designed to mount horizontally.
The water purifier's dual chamber heads are removable and may be rotated independently, which aids in the
installation, maintenance or the retrofitting of an existing system.
The water purifier's chamber, and chamber heads are electropolished and passivated type 316 stainless steel.
Easy-off end caps allow for quick and easy lamp change, without disconnecting the system from the water supply
or draining the purifier. No tools are required.
P
RINCIPLE OF OPERATION
The Bio-Logic design has been carefully conceived to provide adequate germicidal dosage throughout the dis-
infection chamber. The dosage, as it applies to ultraviolet disinfection, is a function of time, and the intensity, of ultra-
violet radiation, to which the water is exposed. The exposure time, in seconds, is the total time it takes the water to
flow through the disinfection chamber, exposing it to the germicidal lamp. Exposure time is related to the flow rate; the
higher the flow rate, the lower the exposure time or the lower the flow rate, the higher the exposure time. The ultravio-
let intensity is the amount of energy, per unit time, emitted by the germicidal lamp. The Dosage is the product of ultra-
violet intensity and the exposure time. The operation of the Bio-Logic is as follows:
1. Water enters the purifier and flows into the annular space between the quartz sleeve and the chamber wall.
2. Suspended microorganisms are exposed to the ultraviolet rays emitted by the germicidal lamp.
3. The LED indicator light, located on the ballast, provides visual indication of germicidal lamp operation.
4. Water leaving the purifier is instantly ready for use, no further contact time is required
LIMITATION OF USE
The water purifier is intended for the use with visually clear water, not colored, cloudy or turbid.
See “Water Quality” section below.
The water purifier is NOT intended for the treatment of water that has an obvious contamination or intentional source,
such as raw sewage; nor is the unit intended to convert wastewater to microbiologically safe drinking water.
WATER QUALITY
Water quality plays a major role in the transmission of germicidal ultraviolet rays. It is recommended that the water
does not exceed the following maximum concentration levels:
Table 1 - Maximum Concentration Levels
Effectively treating water with higher concentration levels than listed above can be accomplished, but may require
added measures to improve water quality to treatable levels. If, for any reason, it is believed the ultraviolet transmission
is not satisfactory, contact the factory.
Manganese: 0.05mg/l
Total Suspended Solids: 10 mg/l
pH: 6.5 - 9.5
Color: None
Hardness: 6 GPG or 102.6 PPM
Iron: 0.3 mg/l