Technical data

BD / ED / FD 01/2006 page 28/49
1. Press down
button for approx. 5 seconds.
The display alternately shows “unit” and in the entry level the temperature unit:
2. Press again button
.
The display alternately shows “rASd” and in the entry level the set-point gradient:
3. Press again button
.
The display alternately shows “Adr” and in the entry level the actual setting of the unit address:
4. Set the required address with buttons .
You can enter address values between 1 and 30.
5. The set value is automatically adopted after 2 seconds.
7.5 General notes
60 sec. after the last entry the controller returns to normal display (actual value display).
The functions set-point entry (chap. 7.1), time functions (chap. 7.3), and calling up the user
menu (chap. 7.4) can only be selected from normal display (actual value display).
When selecting the functions set-point entry and time functions, and when selecting the user
menu functions, the respective button
or must be pressed down for a about 1 sec.
Shorter pressing will be ignored by the controller.
After a power failure, the timer returns to the previous status. A remaining time, if any, will
continue running down.