Datasheet

Product data sheet
Automation technology - data transmission and power
supply
Product description Contacts: 4, Cable outlet: 5 - 8 mm, male angled connector, CRIMP connection, shieldable, CAT 5
Area M12-D, M12-X Series 825 D-coding
Order number 99 3721 820 04
Security notices
The connector must not be connected or separated under load. Non-observance and incorrect use can result in
personal injury.
The connectors are designed for use in plant, control system and electrical equipment. The end user is responsible
for checking whether the connectors are suitable for use in other applications.
To prevent the connector being opened unintentionally when used in electrical circuits containing hazardous life
parts, the thread between the housing and the connector head must be secured using a suitable cyanoacrylate
adhesive. This does not apply to connectors used in SELV and PELV circuits according to IEC 61140 (EN 61140, VDE
0140-1).
Connectors used in electrical circuits containing hazardous life parts must only be assembled and used by or under
the supervision of persons with the requisite electrotechnical training, taking the applicable regulations and
standards into account.
Connectors with degree of protection IP 67 and IP 68 are not suitable for use under water. When used outdoors, the
connectors must be separately protected against corrosion. For further information about IP degrees of protection
refer to ‘Technical support’ in the Download Centre.
To lock the cable connector to the equipment connector, the threaded ring is tightened until it is ‘finger-tight’
(approx. 50 cNm).