Programmer Owner manual
34
IQ
®
Programmer Reference Manual
AX - Alarm Reset (Buffered)
Compatibility: All drives
Affects: Alarm Code
See also: AR, ME, OF, WT Commands
Clears Alarms and Drive Faults. This command functions the same as AR (Alarm Reset) but is a Buffered type command.
Typically used in conjunction with OF within a Q program. Please note that while immediately executing AX will clear the alarm
code, it does not guarantee that the condition that caused the alarm has been resolved. Therefore it is recommended to include a
short delay or wait for user input before clearing the alarm and resuming normal operation.
In addition to clearing alarms and faults, the AX command resets the LED blink timer. As such, if the AX command is used within a
tight loop in a Q program, the LED may actually appear to be solid green.
NOTE: Does not re-enable the drive. Use ME (Motor Enable) command to re-enable drive.
Command Details:
Structure AX
Type BUFFERED
Usage WRITE ONLY
Non-Volatile NO
Register Access None
Examples:
Command Drive sends Notes
In segment 1 of a Q program...
OF9 - When a drive fault occurs load and execute program segment 9
In segment 9 of the same Q program...
WT0.1 - Short delay to allow the system to settle
AX - Alarm reset
ME - Motor enable
QX1 - Load and execute segment 1, which will also reset the OF function.