Product Manual
WWW.BIGASSFANS.COM © 2015 DELTA T LLC ALL RIGHTS RESERVED.
17
3. Secure yoke (to supports)
ATTENTION
Ensure the position locking pin is secured prior to attaching the fan yoke to the supports.
Attach the fan yoke to the supports with the Wall/Column Mount Hardware. Tighten the nuts.
After installation, the fan must be inspected to verify it is suciently secured to the column. Depending on the size
and surface of the column, the fan may be more prone to rotate if subjected to a lateral force.
Wall/Column Mount Hardware:
a. (1) 3/4-10 x 3-1/2” Hex Bolt
b. (2) 3/4” Flat Washer
c. (1) Yoke Attachment Bracket
d. (1) 3/4-10 Nut
4. Secure safety cable
WARNING: The safety cable is a crucial part of the fan and must be installed correctly. If you have any
questions, call Customer Service.
• Route one end of the safety cable through a
Gripple
®
, and then loop the cable around the
fan yoke and back through the Gripple.
• Route the cable through the second Gripple,
around the column, and then back through
the second Gripple.
• Pull the loose ends of the cable through the
Gripples until the cable is drawn tightly around
the column and fan yoke.
• Secure the loose ends of the cable with the
two (2) wire rope clips and torque to 4.5 ft·lb
(6.1 N·m).
Proceed to “Electrical Installation.”
Note: To back the safety cable out of the Gripple, insert a
1/16” (1.5 mm) Allen wrench into the small hole on the Gripple.
a
b
c
b
d