POWER WIRING
Refer to the input voltage rating marked on the fixture, and then wire according to
the diagram and table below.
Supply voltage
Fixture’s L1 (black)
connects to
Fixture’s L2 (white)
connects to
120 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
H (black) N (white)
208 VAC, 3 Ф derived from 3 Ф,
208/120 V panel
L1 (black), L2 (red), or L3
(blue)
L2 (red), L3 (blue), or L1
(black)
240 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
L1 (black) L2 (red)
240 VAC, 1 Ф derived from 3 Ф,
240/120 V panel, B phase wild
L1 (black), L2 (orange), or
L3 (blue)
L2 (orange), L3 (blue), or
L1 (black)
277 VAC, 1 Ф derived from 3 Ф,
480/277 V panel
L1 (brown), L2 (orange), or
L3 (yellow)
N (white)
GROUND GREEN IN US/CA; GREEN W/
YELLOW OUTSIDE US/CA
L1 BLACK IN US/CA; BROWN
OUTSIDE US/CA
L2 WHITE IN US/CA; BLUE
OUTSIDE US/CA
FIXTURE
GROUND
L1
L2
POWER
Low voltage fixture (120–277 V ± 15%)