Instructions

48
English
DC2412-UPSD
|
DC2412-UPS-LDD
|
UPSIC-1205D
|
UPSIC-2403D
15 List of commands
The command index is always 0x03.
GetInputVoltage() 0x25
This read-word function shows the measured input voltage of the UPS.
Cmd Name Access Type Min. Max Unit
0x25 GetInputVoltage() R Int16 0 32768 mV
Transfer packet: 0x01 0x03 0x03 0x25 0x04
GetOutputVoltage() 0x27
This read-word function shows the measured output voltage of the UPS.
Cmd Name Access Type Min. Max Unit
0x27 GetOutputVoltage() R Int16 0 32768 mV
Transfer packet: 0x01 0x03 0x03 0x27 0x04
GetInputCurrent() 0x28
This read-word function shows the measured input current of the UPS.
Cmd Name Access Type Min. Max Unit
0x28 GetInputCurrent () R Int16 0 32768 mA
Transfer packet: 0x01 0x03 0x03 0x28 0x04
GetChargeCurrent() 0x29
This read-word-function shows the measured charge current of the UPS.
Cmd Name Access Type Min. Max Unit
0x29 GetChargeCurrent () R Int16 -32768 32768 mA
Negative numbers indicate a discharge.
Transfer packet: 0x01 0x03 0x03 0x29 0x04
GetCapStackVoltage() 0x26
This read-word-function shows the measured voltage at the capacitor stack of the UPS.
Cmd Name Access Type Min. Max Unit
0x26 GetCapStackVoltage() R Int16 0 32768 mV
Transfer packet: 0x01 0x03 0x03 0x26 0x04