Instructions
DC2412-UPSD | DC2412-UPS-LDD | UPSIC-1205D | UPSIC-2403D
17
Deutsch
12.7 DIP-Switch
Der interne DIP-Switch kann über die dargestellte
Öffnung im Gehäuse konfiguriert werden.
DIP-Switch-Einstellungen
1
ON
23456
CAPS FULL
SD(RB)PF
Shutdown Timer
PIN 2 1
No Reboot ON ON
Reboot after 10s OFF ON
Reboot after 30s ON OFF
Reboot after 60s OFF OFF
ON Output released
when V
CAP
over 90 %
Output release
PIN 3
Power Fail (PF) - Timer
6 5 4 PIN
ON ON ON Software
OFF ON ON 3s
ON OFF ON 8s
OFF OFF ON 20s
ON ON OFF 40s
OFF ON OFF 60s
ON OFF OFF 100s
OFF OFF OFF 150s