Data Sheet

UPSIC-2403D
24 V DC / 3 A
Regulated voltage at backup
Maintenance-free supercaps for energy storage
High cycle stability > 500 000
Charge time <60 sec at maximum charge current
Extended temperature range -20…+70 °C
Compact DIN rail chassis
Active reverse polarity protection
Power Fail signal via relay, RS232 connection
Intelligent charge sharing
Reboot Function
Operation of UPS at host without software possible
Output release from 90 % supercap capacity
Input voltage 24 VDC (22.5…30 VDC)
Input current 3.5 A
Output power 70 W
Output voltage battery mode 24 VDC ±2 % regulated
Output voltage normal mode Vin–0.2 V at 100 % load
Output current 3 A
Output ripple ≤40 mV
Efficiency 94 % (V
Supercap
9.5V, I
out
1.25 A)
Charge current Depending on load up to 6.2 A CC (V
Supercap
)
Charging method CC / CV
Storage type Supercaps 4x 100 F
Charging time <60 sec at maximum charge current @ 4x 100 F
Backup time See diagram
Protection Overcurrent protection – Non LATCH
Active reverse polarity protection
Safety / EMC CE
Temperature Operating: -20…+70 °C / Storage: -20…+70 °C
Humidity Operating: 10…85 % RH, non-condensing / Storage: 10…90 % RH, non-condensing
Dimensions (W x D x H) 36 x 103 x 147 mm
Weight (net) 0.367 kg
Bicker Elektronik GmbH | 86609 Donauwörth | Germany
Tel. +49 906 70595-0 | info@bicker.de | www.bicker.de
Operation