Data Sheet
UPSIC-1205D
12 V DC / 5 A
Regulated voltage at backup
Maintenance-free supercaps for energy storage
High cycle stability > 500 000
Charge time <60 sec at maximum charge current
Extended temperature range -20…+70 °C
Compact DIN rail chassis
Active reverse polarity protection
Power Fail signal via relay, RS232 connection
Intelligent charge sharing
Reboot Function
Operation of UPS at host without software possible
Output release from 90 % supercap capacity
Input voltage 12 VDC (11.6…16 VDC)
Input current 5.8 A nom.
Output power 60 W
Output voltage battery mode 12 VDC ±2 % regulated
Output voltage normal mode V
in
– 0.3 V at 100 % load
Output current 5 A
Output ripple ≤30 mV
Backup efficiency 97 % (V
Supercaps
9.5 V, I
out
2.5 A)
Charge current Depending on load up to 6.2 A CC (V
Supercap
)
Charging method CC / CV
Storage type Supercaps 4x 100 F
Charging time <60 sec at maximum charge current @ 4x 100 F
Backup time See diagram
Protection Overcurrent protection – Non LATCH
Active reverse polarity protection
Safety / EMC CE
Temperature Operating: -20…+70 °C / Storage: -20…+70 °C
Humidity Operating: 10…85 % RH, non-condensing / Storage: 10…90 % RH, non-condensing
Dimensions (W x D x H) 36 x 103 x 147 mm
Weight (net) 0.367 kg
Bicker Elektronik GmbH | 86609 Donauwörth | Germany
Tel. +49 906 70595-0 | info@bicker.de | www.bicker.de
Operation
Operation
Delivery
5
YEARS
Delivery
5
YEARS
Fanless
Fanless Extended
Extended
Eco
Eco
Including
Software
UPS Control Center
NEW
UPS systems
DC UPS
Technical data