Instructions
UPSI-1208(D) | UPSI-2406(D)
28
Deutsch
GetOutputVoltage() 0x27
This read-word function returns the measured output voltage of the UPS.
Cmd Name Access Type Min. Max Unit
0x27 GetOutputVoltage() R Int16 0 32768 mV
Transfer packet: 0x01 0x03 0x03 0x27 0x04
GetInputCurrent() 0x28
This read-word function returns the measured input current of the UPS.
Cmd Name Access Type Min. Max Unit
0x28 GetInputCurrent () R Int16 0 32768 mA
Transfer packet: 0x01 0x03 0x03 0x28 0x04
GetChargeCurrent() 0x29
This read-word function returns the measured charge current of the UPS.
Cmd Name Access Type Min. Max Unit
0x29 GetChargeCurrent () R Int16 -32768 32768 mA
Transfer packet: 0x01 0x03 0x03 0x29 0x04
22.4 Command Index “Battery A” and “Battery B” 0x04 / 0x05
GetBatteryTemperature() 0x08
This read-word function returns the measured temperature.
Cmd Name Access Type Min. Max Unit
0x08 GetBatteryTemperature() R Uint16 0 65535 0.1°K
Transfer packet: 0x01 0x03 0x04 0x08 0x04
GetBatteryVoltage() 0x09
This read-word function returns the sum of measured cell voltages.
Cmd Name Access Type Min. Max Unit
0x09 GetBatteryVoltage() R Uint16 0 65535 mV
Transfer packet: 0x01 0x03 0x04 0x09 0x04