22.2 Command Index “Sensors” 0x02
GetCPUTemperature() 0x00
This read function returns the cpu temperature.
Cmd Name Access Type Min. Max Unit
0x00 GetCPUTemperature() R Uint16 0 +150 °C
Transfer packet: 0x01 0x03 0x02 0x00 0x04
GetOutputCurrent() 0x01
This read function returns the output current.
Cmd Name Access Type Min. Max Unit
0x01 GetOutputCurrent () R Int16 0 +32768 mA
Transfer packet: 0x01 0x03 0x02 0x01 0x04
GetInputVoltage() 0x02 (not connected at moment)
This read function returns the input voltage.
Cmd Name Access Type Min. Max Unit
0x02 GetInputVoltage () R Int16 0 +32768 mV
Transfer packet: 0x01 0x03 0x02 0x02 0x04
22.3 Command Index “Charge Controller” 0x03
GetEnergyStorageVoltage() 0x20
This read-word function returns the measured voltage of the capacitor 1.
Cmd Name Access Type Min. Max Unit
0x20 GetEnergyStorageVoltage () R Int16 0 32768 mA
Transfer packet: 0x01 0x03 0x03 0x20 0x04