Data Sheet
UPSI-2406D
24 V DC / 6 A
24V DC UPS (DIN rail version)
Intelligent power sharing
Regulated output voltage
Min. load disconnect
Battery disconnect
Power fail timer
Battery start function
External signal shutdown
Battery hot swap
Reboot function
Fuel gauge
Input voltage 24 V DC (22.5…29 V)
Input current 7.5 A max.
Output voltage Normal mode: V
in
– 0.3 V (Full load)
Backup: 23.5 V DC
Output current 6 A max.
Battery charge current nom. 3 A max. on input
Charging method CC / CV / CP
Protection Deep discharge protection
Overcurrent protection
Reverse polarity protection
Interface USB, RS232, USB-HID
Type of battery LiFePO4, Supercaps
Safety / EMC CE
Temperature Operating: -20…+70 °C / Storage: -20…+70 °C
Derating (depending on temperature) Backup mode: +55…+70 °C, 100 mA (2.35 W) / °C
Max. operation altitude 5000 m
Derating (depending on operation altitude) 1500 m operation altitude or higher:
5.7 W / 500 m or reduction of operation temperature of 3.5 °C / 500 m
Humidity Operating: 10…85 % RH, non-condensing / Storage: 10…90 % RH, non-condensing
Dimensions (Wx D x H) 36 x 100 x 120 mm ±0.5 mm
Weight (net) 0.25 kg
Bicker Elektronik GmbH | 86609 Donauwörth | Germany
Tel. +49 906 70595-0 | info@bicker.de | www.bicker.de
Operation
Operation
Delivery
5
YEARS
Delivery
5
YEARS
Fanless
Fanless
Eco
Eco
Technical data
UPS systems
DC UPS
Extended
Extended
NEW
Product specific data
Battery monitoring Battery test is executed in normal mode
Shutdown detection Via load sensor
Reboot function Reboot function and time can be configured by software
Load sensor Configurable via UPSI HID-Battery-Parameter software (download at www.bicker.de)
UPS shuts down after 15 sec, if connected load decreases below set value and UPS is being in battery mode
Timer function Configurable via UPSI HID-Battery-Parameter software in steps of single seconds (3600 sec max)
External signal shutdown UPS can be configured to shut down on external signal (e.g. ignition)
with delay set in steps of single seconds (3600 sec max)
Backup time See datasheets of battery packs
Relay Dry contact on power fail (Normal mode: open / Backup mode: closed)
Relay switching current max 0.5 A @ 125 V AC / 1 A @ 24 V DC
Also available as
open frame version
UPSI-2406