User’s Manual UPSI-2403
5 Installation and Start up
Connections
No tes
The DC UPS UPSI-2403 must be mounted horizontally.
Ensure there is sufficient convection during operation.
All connector cables must be dimensioned for the input current of the
UPSI-2403 (6.7 A) and an according additional protection must be provided and
fused. The recommended cross section for the connector cables is 1.5 mm
2
.
Before switching on the unit, make sure all connections are correct.
Both fuses (10 A Mini®Fuse) must be engaged.
UPSI-2403
Status
Fuse 1Fuse 2
USB
DC
|
UPS 24V/ 6 A
IN +
IN –
OUT
OUT +
1
2
3
4
5
IN+
GND
IN+
USB
IN
-
UPSI | Control Center
The UPS software is available for download
at www.bicker.de. In addtion to the current
operating parameters, the software informs
about the expected „battery lifetime“, too.
UPSI-2403
DC UPS System
24 VDC / 6 A