Operator`s manual

14
Reading Configuration Menu
56
14.4 FILtER Enter FILTER CONFIGURATION SUBMENU:
Press ‘RESET/ENTER 12) Display shows "CNt by" Counter by or round-off feature. To enter,
Press ‘RESET/ENTER’).
Press ‘MENU 13)
Scroll through 3 available selections of Filter configuration: "CNt by",
"FILt.tP" and "FILt.tM". Refer to the flowchart below.
CNt by Enter COUNT BY FILTER FUNCTION MENU:
Press ‘RESET/ENTER 14) Display flashes "001" (default) or previous setting value.
Press ‘/MAX 15)
Scroll though 7 available selections: 001, 002, 005, 010, 020, 050 and
100 for your choice of setting.
Press ‘RESET/ENTER 16)
Display advances to "FILt.tP" Filter Type Selection Menu. If a change
was made, the controller will also show "StOREd" stored message
momentarily.
FILt.tP Enter FILTER TYPE SELECTION MENU:
Press ‘RESET/ENTER 17) Display flashes "A.b.C.F IL" Adaptive Bandwidth Control Filter.
Press ‘/MAX 18) Scroll through 2 supported types: "A.b.C.F IL" or "MOV.AVE" (Moving
Average) for your desired option.
Press ‘RESET/ENTER 19)
Display advances to "FILt.tM" Filter Type Selection Menu. If a change
was made, the controller will also show the "StOREd" stored message
momentarily.
FILt.Tm Enter FILTER TIME SETTING MENU:
Press ‘RESET/ENTER 20) Display flashes "004" (default) or previous setting value.
Press ‘/MAX 21) Scroll though 8 available selections: 001, 002, 004, 008, 016
, 032, 068
and 128 for your choice of setting.
Press ‘RESET/ENTER 22) Display advances to "FLS.dSP" Flashing Display Setting Menu. If a
change was made, the controller will also show the "StOREd" stored
message momentarily.
FILtER
CNt by
(Count By)
FILt.tP
(Filter Type)
001 002 005 010 020 050
100
FILt.tM
(Filter Time)
A.b.C.FIL
(Adaptive Bandwidth Control Filter)
MOV.AVE
(Moving Average)
001 002 004 008 016 032
064
128