Technical information

Bewacard 610 Technical Manual 7
How to select connecting cables
It is important to use cables with the correct conductor gauge, to keep
the voltage drop in the cables as low as possible.
12 volt supplies. A 12 V electric locking device generally needs at
least 11 V to work properly, so the voltage at the card reader
should never be less than 11 V.
24 volt supplies. A 24 V electric locking device generally needs at
least 21 V to work properly, so the voltage at the card reader
should never be less than 21 V.
The recommended gauge (cross-sectional area) of the conductor
depends on the distance between the power supply and the card reader,
and on the load at the card reader.
The table below is for a Bewacard 610 with an electric release. The
total load is 300 mA at 24 V or 600 mA at 12 V.
24 V Supply
12 V Supply
Cable
length
(metres)
Min conductor
Min conductor
area
(mm
2
)
dia
(mm)
area
(mm
2
)
dia
(mm)
0-50 0.17 0.46 0.51 0.80
51-100 0.34 0.65 1.02 1.14
101-150 0.51 0.80 1.53 1.40
151-200 0.68 0.93 2.04 1.61
201-250 0.85 1.04 2.55 1.80
251-300 1.02 1.14 3.06 1.95