Installation manual
TYPICAL REMOTE UPRIGHT INSTALLATION (Top Mount)
MAINTENANCE & REPAIR 105
NOTE:
1. All refrigeration and electrical materials between
condensing unit and cabinets are to be supplied by
the installing contactor.
2. Suction lines must be insulated with 1/2" thick
aramflex or equal their entire length.
3. Refrigeration lines should be run as short and direct
as possible.
4. To aid oil drainage, horizontal suction lines should be
pitched downward at least 1/2" per 10 feet of run.
5. To insure oil return, a āPā trap must be installed in the
suction line a the foot of every riser.
6. Liquid line not shown - Do not run liquid line inside
insulation with suction line.