User`s manual
Installation and Wiring
GFK-1742A Chapter 3 Installing and Wiring the DSM314 3-23
3
8
.51
9
.84
1.38
1.11
0
.58
Figure 3-14. 44B295864-001 Grounding Bar Dimensions, Rear View Showing Mounting Holes
3.
For installations which must meet IEC electrical noise immunity standards, a Cable Shield
Grounding Clamp A99L-0035-0001 and one of the 11 available slots on the Grounding Bar
44B295864-001 must also be used at the Digital Servo Axis Terminal Block end of the servo
amplifier cable IC800CBL001/002. If the Digital servo amplifier cable is connected directly
to the DSM314 faceplate (no Digital Servo Axis Terminal Block used) the Grounding Clamp
and Bar are not required at the faceplate end of the cable.
For additional information, refer to
Installation Requirements for Conformance to Standards
,
GFK-1179.
90-30
HIGH
CAPACITY
POWER
SUPPLY
MDL AI
CPU 360
MDL AO
DSM 314
M
A
M
P
Axis
Terminal
Block
Grounding Bar
44B295864-001
Grounding Clamp
A99L-0035-0001
(Always Required)
DSM314 to Axis Terminal
Block Shielded Cable
Terminal Block to Servo Amp
Shielded Cable
Faceplate Shield Ground Wire
(Always Required)
Grounding Bar 44B295864-001 and
Grounding Clamp A99L-0035-0001
(Required for CE Mark Installation)
Strobe and Limit
Switch Signals
Ground Wire to "S" Terminal
(Always Required)
Figure 3-15. DSM314 I/O Cable Grounding