User`s manual

Getting Started
GFK-1742A Chapter 2 Getting Started 2-37
2
Section 5: Testing Your System
Generating Motion
CAUTION
For correct machine operation, the recommended start-up procedure must be
performed. This includes validating operation of the Overtravel Limits and
Home Switch, checking for correct motor rotation direction, and tuning the
velocity and position loops. This must be done by experienced personnel. For
detailed start-up instructions, refer to Appendix D,
Start-Up and Tuning a GE
Fanuc Digital or Analog Servo System.
Enabling Run Mode on the PLC
The next step in the DSM314 system operation is to place the PLC in the RUN mode.
1. From the VersaPro main menu, choose the PLC menu selection. From the P
LC submenu,
choose Connect. The Connect menu will appear. From this menu select the communications
method/port that you wish to use to communicate with the PLC. If you have not yet
configured the communications port, consult the VersaPro documentation GFK-1670 or the
VersaPro 1.1 on-line help for further information.
2. From the VersaPro main menu, select the Tools menu selection. From the T
ools submenu
select Fault Table entry. This will bring up the PLC fault table display. Review the fault
tables for any problems and then use the function key F9 Clear to delete any PLC faults
present. Select the I/O fault table tab and perform the same operation on these faults as well.
Close the fault table and return to the VersaPro main screen
3. From the VersaPro main menu, select the PLC menu selection. From the P
LC submenu select
the Run entry. This will place the PLC in run mode.
Warning
Make sure that your motor is properly fastened down. If not, the motor
could be damaged and/or cause injury to personnel.
4. Visually check that the PLC LEDs labeled PWR, OK, and RUN are all on. Visually check
that the DSM314 module LEDs STAT, OK and CFG are on. For
α
Series Digital amplifiers,
visually check that the amplifier status readout is showing a minus sign () (which indicates
Standby Mode). For
β
Series Digital amplifiers check that the Power LED is on and the ALM
LEDs are off. For SL Series amplifiers, check the front panel display on each amplifier for
any errors (as indicated by all digits on the display flashing on and off).
5. If an amplifier indicates a fault, it may be necessary to completely remove power from the
amplifiers and the PLC and repeat the power on sequence described in Section 3.
6. Assuming no errors are present, you should be able to jog the attached axes. For the startup
configuration previously described, to clear any error indicated by the DSM314s STAT LED