F-2 Motion Mate™ DSM314 for Series 90™-30 PLCs User's Manual
–
January 2001 GFK-1742A
F
space on the hard drive. To run from the floppy, type install at the A:\> or B:\>
prompt.
7. (DOS) From the main menu, press the F3 key to configure the correct serial port if the cable
is not connected to COM1. Press the TAB key to toggle through the options, and
ENTER to accept the displayed choice.
8. (DOS) From the main menu, press the F1 key to attach to the DSM302 slave device.
9. (DOS) Once the slave device is attached, the boot mode menu will appear - press F1 to enter
BOOT MODE and press the ‘Y’ key to confirm the operation. The STAT and CFG
LED’s on the front of the module should now be flashing in unison.
10. (DOS) Once in boot mode, press the F1 key to download the new firmware.
11. (DOS) Press the
Y
key to confirm the operation. The download should take about 4
minutes. If the download fails, refer below to
Restarting An Interrupted Firmware
Upgrade
.
12. (DOS) When the download is complete , the PC loader will instruct you to power cycle your
module. At this time, power cycle the module. If the module is installed in an
expansion or remote rack, it is necessary to also power-cycle the main rack.
13. (DOS) Label the unit with the installed firmware version. If the firmware is Beta or an
Engineering Release, indicate so on the label.
Windows Update (For Windows 95/NT/98, NOT Windows 3.1)
Note: This section only applies to those using the Winloader update software with
Windows 95, NT, or 98. If using the DOS operating system, see the section “DOS
Update.”
5. (WIN) Insert a labeled floppy disk in drive A: or B:. Ensure that the floppy is not
write protected. Run the self-extracting archive specifying drive A: or B: as
the destination when prompted with "Unzip to folder".
6. (WIN) Invoke the Winloader software package by double clicking on its icon located
in drive A: or B: (depending on the drive designation for the 3.5” floppy disk)
in Windows Explorer or simply execute it by going to the start menu and
selecting RUN. In the RUN window type A(or B):winloader.exe.
7. (WIN) Begin storing firmware by single clicking the “Update” button.
8. (WIN) Upon completion of the update a window will “pop up” indicating the status of
the update. If the update was successful, power cycle the PLC and indicate
that another device is NOT to be updated by left clicking on “No”. If not
successful, try changing the Settings/Update Baud rate from 38400 to 19200
and repeat the procedure.
Restarting an Interrupted Firmware Upgrade
A. Connect all cables as described in step 4 of the procedure above.
B. Power cycle the rack containing the module. If a partial or erroneous download was
performed, the module will power up with the STAT and CFG LED’s on the module
flashing in unison.
C. If you are still running the PC Loader or Winloader program on your PC, skip to step
D below; otherwise, follow steps 5 and 6 above.
D. Follow step 7 above. Note that you will automatically be placed in BOOT MODE.
E. Follow steps 9 through 12 above.
F. If the update still fails, repeat the process with a lower baud rate.
G. Label your unit with the installed firmware version.
MS-MS-DOS, Windows, and Windows NT are registered trademarks of Microsoft Corporation;
Pentium is a trademark of
Intel Corporation; IBM-AT and IBM-PC are registered trademarks of International Business Machines Corporation.