Next, you must select the power supply and CPU that are appropriate for your installation. Note
that Local Logic requires that the CPU be equipped with firmware release 10.00 or higher. The
default “CPU351” CPU does not support release 10.00 firmware, but the “CPU363” CPU does;
therefore, we are going to change the CPU to the “CPU363” model. The steps are:
•
Right-click the CPU on the hardware configuration screen and select Replace CPU from the
short-cut menu. A module selection box will appear.
•
Click the IC693CPU363 item, then click the OK button
•
Two message boxes will appear warning that (1) replacing a CPU cannot be undone, and (2)
the SNP and other parameters are always carried over, etc. In both cases, click Yes to proceed.
•
The CPU363 configuration window will appear. Make any desired configuration edits, then
close the configuration window.
If necessary, consult the VersaPro documentation or on-line help for more details. The resulting
display will appear as shown in Figure 16-30.
Figure 16-30. Hardware Configuration 90-30 rack with CPU363