User`s manual

2-6 Motion Mate DSM314 for Series 90-30 PLCs User's Manual
January 2001 GFK-1742A
2
SVU Amplifier Channel Switches
Confirm that the Channel Switches (DIP
switches), located behind the SVU amplifier
door, are set as shown in the following
tables. Note that the
OFF
position is to the
left, and the
ON
position is to the right.
Note also, that the switches are numbered
from bottom to top (Switch 1 is the bottom
switch). For example, in Figure 2-3,
Switches 1, 3, and 4 are shown ON, and
switch 2 is shown OFF
Figure 2-3. SVU Amplifier Channel Switches
Table 2-1. SVU Amplifier Channel Switch Settings
Amplifier SVU1-80
Regenerative Discharge Unit SW1 SW2 SW3 SW4
Built-in (100 W) ON OFF ON ON
Separate A06B-6089-H500 (200 W) ON OFF ON OFF
Separate A06B-6089-H713 (800 W) ON OFF OFF OFF
Amplifier SVU1-130
Regenerative Discharge Unit SW1 SW2 SW3 SW4
Built-in (400 W) ON OFF ON ON
Separate A06B-6089-H711 (800 W) ON OFF ON OFF
(To connect additional amplifiers, repeat steps B, C and D above for each additional amplifier.)
OFF
ON
4
3
2
1
ON